The MFR012 is designed to control the relative air humidity inside of enclosures. When connected to an enclosure heater, (de-humidifier), it will turn the heater on at the set humidity level in order to raise the dew point. This helps prevent damage and malfunction of electronic components caused by condensation and corrosion. The MFR012 can also be used to control cooling fans, warning lights or other devices.

SPECIFICATIONS
Adjustment Range: 35 to 95% (±3.0%) relative humidity Switching Difference (Hysteresis): Approx. 4% RH @ 50% relative humidity
Permissible Air Velocity: 50 ft/sec (15 m/s)
Maximum Switching Voltage: 250 Vac
Attention: 250 V should only be switched in a non-condensing environment
Contact Type: Change-over contact
Contact Resistance: <10 mΩ
Service Life: 100,000 cycles
Minimum Switching Capacity: 100 mA @ AC/DC 20 V
Maximum Switching Capacity: 5A @ AC 230V (resistive load), 1.0A @ AC 230V (inductive load at cos j = 0.8); DC 20W
EMI/EMC Compliance: EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection: 3-pole terminal, 3 x AWG 14 max [2.5 mm2 (0.1 in2)]
Mounting: Clip for 35mm (1.4") DIN rail (EN 50022)
Dimensions: 67H x 50W x 38 mmD (2.64 x 1.97 x 1.5")
Housing: Clip for 35mm DIN rail (EN 50022)
Weight: 60g (2oz)
Operating Temperature: 0 to 60°C (32 to 140°F)
Storage Temperature: -20 to 80°C (-4 to 176°F)
Protection Type: NEMA 2 (IP20)
Application Examples:
   • Electrical and Electronic Enclosures
   • Telecommunication Systems
   • Display Panels
   • Ticket Dispensers
   • Automatic Teller Machines (ATM’s)
   • Access and Parking Control Systems
Note: The critical relative humidity for most components is 65%. Above 65% RH, condensation can cause malfunction of electronic equipment. Long-term, this can lead to corrosion and permanent damage of electronic components and systems.
注文する (部品番号ビルダーより掲載以外の製品もご選択いただけます)(注文数を入力の上、"カートに追加"をクリックしてください)
部品番号/Desc.
注文数
商品説明
MFR0122
お問い合せ下さい   
納期: 
 
 
Mechanical humidity control, SPDT, 35 to 100% RH, 20 Vdc to 230 Vac
注: Comes with complete operator’s manual.
Ordering Example: (1) MFR0122 Mechanical hygrostat, ¥25,745 
We noticed you are from the US. Visit your local site for regional offers and live support.